Jiangsu Yawei Transformer Co., Ltd. yog ib qho ntawm cov tuam txhab ua lag luam thiab cov neeg muag khoom ntawm 25mva 25000kva 150kv kauj ruam qis zog transformer nrog mr oltc hauv Suav teb. Thov koj xav tias dawb mus yuav zoo 25mva 25000kva 150kv kauj ruam nqes fais fab transformer nrog mr oltc los ntawm peb lub hoobkas. Customized xaj yog txais tos.
Khoom Taw Qhia
YAWEI's 25MVA 150KV OLTC lub zog hloov pauv tau xa mus rau Ltalis xyoo 2024, qhov 25000KVA ntsuas hluav taws xob hloov pauv tau ua haujlwm hauv cov cement cog raws li hauv Sicily, qhov hluav taws xob hloov hluav taws xob no yog tsim nrog ONAN / ONAF txias txoj kev thiab thawj qhov hluav taws xob yog 150KV, theem nrab voltage yog 6.5KV. Tus ntawm -load tap changer muaj 25 kauj ruam ± 12 × 1.5% (± 18%).
Qhov zoo ntawm peb cov khoom
YAWEI ua kom ntseeg tau tias txhua yam ntawm peb cov transformers xa tawm tau dhau qhov kev sim nruj tshaj plaws .Txawm li cas los xij, peb tseem tshuav 0 cov ntaub ntawv tsis raug rau ntau tshaj 10 xyoo thiab peb cov roj immersed fais fab transformer yog tsim los ntawm IEC, ANSI thiab lwm cov qauv loj thoob ntiaj teb kom deb li deb. Peb tau xa tawm mus rau 50+ lub teb chaws thoob ntiaj teb thiab tau txais daim ntawv pov thawj cuam tshuam hauv cheeb tsam. Qhov kawg tab sis tsis kawg, lub siab voltage transformer tuaj yeem tsim raws li cov neeg siv khoom xav tau.
Peb lub hom phiaj yog los ua koj tus neeg muag khoom zoo tshaj plaws thiab cov koom tes ua lag luam, txais tos rau peb kom tau txais cov ncauj lus kom ntxaws zog transformer cov phiaj xwm.
25 MVA 150/6.5KV Transformer Chaw tsim tshuaj paus


Thaum lub sij hawm lub installation txheej txheem, peb feem ntau muaj ob txheej txheem los xyuas kom meej lub efficiency ntawm installation.
25MVA 150/6.5KV Transformer Test

Thaum lub sijhawm kuaj, peb yuav sim qee cov ntaub ntawv tsim nyog, piv txwv li: Kev ntsuas qhov tso tawm ib nrab, qhov ntsuas qhov sib piv, DC tsis kam kuaj, ntsuas impedance, tsis muaj -load test, kev xeem, kev ntsuas kev tiv thaiv kev tiv thaiv, muaj peev xwm ntsuas, roj dielectric poob xeem, AC withstand voltage test, withstand voltage test, poob parameter test, inductance test, thiab lwm yam .... kom paub meej tias peb cov khoom tsis muaj teeb meem ua ntej.
Ntim thiab xa khoom

Ntim: Peb feem ntau siv cov ntaub ntawv ntoo lossis raws li cov neeg siv khoom xav tau rau pob.Hais txog qhov yuav tsum tau ua thiab kev txhawb nqa ntawm cov thawv ntim khoom, peb yuav nruj me ntsis siv rau cov qauv thoob ntiaj teb.
Peb tseem yuav ua kom muaj kev nyab xeeb ntawm cov khoom thaum lub sijhawm thauj mus los
Vim li cas thiaj xaiv YAWEI?
1. Tshaj li 30 xyoo kev paub dhau los hauv kev tsim ntau hom transformers.
2. Pab pawg kws tshaj lij. Txaus siab thiab nyob rau hauv - kev pabcuam sijhawm.
3. Peb cov khoom tau xeem dhau tus qauv zoo thiab tau txais UL, EC, IEC, CNAS, SA, IEEE, ISO9001: 2000 daim ntawv pov thawj zoo
4. Peb muaj qhov systematic, scientific, ib qho kev tsim los ntawm winding casing mus rau lub hwj chim hloov.
5. Peb yuav muab cov khoom zoo tom qab - kev muag khoom installation rau pab neeg txawv teb chaws.
6. Peb txaus siab los tsim kev koom tes ntev nrog cov neeg siv khoom lossis tuam txhab lag luam.
Cim npe nrov: Tuam Tshoj 25mva 25000kva 150kv kauj ruam nqes fais fab transformer nrog mr oltc, Tuam Tshoj 25mva 25000kva 150kv kauj ruam nqes fais fab transformer nrog mr oltc manufacturers, lwm tus neeg, Hoobkas
25 MVA fais fab transformer specification thiab cov ntaub ntawv
| Qauv | SFZ-25000/150 |
| Txuj | IEC60076 |
| Kev teeb tsa | Sab nraum zoov |
|
Ambient kub
|
-25℃~ +40 degree
|
|
Qhov siab
|
Tsawg dua los yog sib npaug li 1000m
|
|
Rated zog
|
25 000 KVA |
|
Rated Voltage -HV winding
|
150 KV TSI
|
| Rated Voltage -LV winding | 6, 5kv |
|
Rated Zaus
|
50 Hz |
|
Txias qhov system
|
ONAN / ONAF (20MVA / 25MVA) |
|
Coj mus rhaub changer
|
OLTC (MR)
|
|
Coj mus rhaub ntau
|
150±12×1.5% (±1 8%)
|
| Cov roj txias |
Mineral roj
|
|
PEI (yuav tsum ua tau raws li qhov yuav tsum tau ua ntawm ecodesign Tier2)
|
Ntau dua lossis sib npaug li 99.7%
|
|
Tsis muaj -load poob
|
13 kWm |
|
Load poob thiab efficiency
(25%, 50%, 75%, 100% ntawm Rated Power)
|
5.87 KW (99.70%)
23.5KW (99.71%)
52.9KW (99.65%)
94.0KW (99.57%)
|
|
Impedance
|
11.5% |
|
Vector Group
|
Yyn 0
|
| BIL (HV winding) |
650 kV ua
|
|
Qhov chaw ntawm HV Bushings
|
Sab saum toj mounted |